6025: Temperature was latched before conversion (OpSys error in ABLS)

Info:
Data type:

Description:
Runtime error while reading the measured motor and heat sink temperatures. The line currents and temperatures are recorded consecutively per cycle (multiplexed). The exact time of the read access to the converted temperature values took place while recording the current. Read access in this timeframe causes incorrect temperature values.

Reaction:
See error number 6021.

Cause/Remedy:
See error number 6024.